GE F650 Instruction Manual page 407

Digital bay controller
Hide thumbs Also See for F650:
Table of Contents

Advertisement

7.2 IEC 61850 PROFILE FOR F650
2.4 Logical Nodes for control. LN Group: C
2.4.1CSWI (Switch controller)
CSWI class
Attribute
Name
CSWI
Data
Common Logical Node Information
Mod
Beh
Health
NamPlt
Controls
Pos
In the F650 there are up to 16 configurable switchgears. Currently four XSWI and four CSWI are implemented and mapped
to first nine swithcgears in F650. XSWI and CSWI Logical Nodes can be seen as paired objects in F650 as one pair of
XSWI and CSWI map to the same swithcgear. XSWI1 and CSWI1 map to Switchgear1, XSWI2 and CSWI2 map to
Switchgear2, etc. The difference between XSWI and CSWI in F650 is that control commands cannot be sent directly via
XSWI LN. Control commands have to be sent via CSWI LN.
In CSWI LN for "Pos" controllable attribute all possible control models are applicable:
"direct-control-with-normal-security"
"SBO-control-with-normal-security"
"direct-control-with-enhanced-security"
"SBO-control-with-enhanced-security"
The sboTimeout attribute for Pos is configurable in a range from 500 ms to 60 seconds.
The sboClass attribute for Pos can only have value "0" (operate-once).
7
7-38
Attribute
Explanation
Type
Switch controller
INC
Mode
INS
Behaviour
INS
Health
LPL
Name plate
geDPC
Switch position
F650 Digital Bay Controller
7 IEC 61850 PROTOCOL
M/O/E
Notes
M
Status-only
M
M
M
M
Switch open, close, undefined