11.1 EXAMPLE 1: COMMUNICATION & PROTECTION SETTINGS PROCEDURE
Under
SETPOINT RELAY CONFIGURATION LEDS
11
Under
SETPOINT RELAY CONFIGURATION OPERATIONS
Select
Command Text
Interlock Type
Interlocks
Final State Type
Final States
Frontal Key
Contact Input
Virtual Output
Time Out
MMI
Com1
Com 2
ETH-Master 1
ETH Master 2
ETH Master 3
ETH Master 4
Under
SETPOINT RELAY CONFIGURATION OSCILLOGRAPHY
Apply 7.5 A in phase A (terminals B1-B2) until contact 00 on Board F operates (terminals F19-F21 should be and remain
closed), and LED 5 should be lit. Check that operating time is in the order of 1.7 seconds.
Remove current from terminals B1-B2
Press pushbutton F1 and check that contact 00 on Board F has been open.
Check that LED 5 in the front of the relay has been turned off.
Repeat the process for phase B (terminals B3-B4) and for phase C (terminals B5-B6)
Under Actual Waveform Capture menu retrieve the last oscillography recording stored, open it using GE_OSC program
and check that the two digital signals as well as the current signal were kept.