7.2 IEC 61850 PROFILE FOR F650
2.3.1.4 hseRDIR
This logical node class is used for sensitive ground directional elements and has 3 instances inside the device.
RDIR class
Attribute
Name
RDIR
Data
Common Logical Node Information
Mod
Beh
Health
NamPlt
Status Information
Dir
Op
Blk
BlkIn
Settings
ChrAng
BlkValV
PolOpMod
BlkMod
RDIREna
Note: ACT includes origin attribute in ST, this is implemented according to Tissue 68.
7
7-36
Attribute
Explanation
Type
Directional Element
INC
Mode
INS
Behaviour
INS
Health
LPL
Name plate
ACD
Direction
ACT
Operate
ACT
Block
ACT
Sens Gnd Dir Blk Inp
ASG
Characteristic Angle
ASG
Minimun operating current
ING
Direction
ING
Block Logical
SPG
Function Permission
F650 Digital Bay Controller
7 IEC 61850 PROTOCOL
M/O/E
Notes
M
Status-only
M
M
M
M
Fixed to unknown value
E
Sens Gnd Dir OP
E
Sens Gnd Dir Block
E
Sens Gnd Dir Blk Inp
O
(-90, 90) MTA
O
(0, 300) Pol V Threshold
E
(Reverse, Forward)
E
(Prmission, Blocked)
E
(Enable, Disable)