Warnings and Alarms
ALARM 94, End of curve
Feedback is lower than the set point. This may indicate
leakage in the system. 22-50 End of Curve Function is set for
alarm.
Troubleshooting
Troubleshoot the system and reset the frequency
converter after the fault has been cleared.
ALARM 95, Broken belt
Torque is below the torque level set for no load, indicating
a broken belt. Parameter 22-60 Broken Belt Function is set
for alarm.
Troubleshooting
Troubleshoot the system and reset the frequency
converter after the fault has been cleared.
ALARM 96, Start delayed
Motor start has been delayed due to short-cycle
protection. Parameter 22-76 Interval between Starts is
enabled.
Troubleshooting
8
8
Troubleshoot the system and reset the frequency
converter after the fault has been cleared.
WARNING 97, Stop delayed
Stopping the motor has been delayed due to short -cycle
protection. Parameter 22-76 Interval between Starts is
enabled.
Troubleshooting
Troubleshoot the system and reset the frequency
converter after the fault has been cleared.
WARNING 98, Clock fault
Time is not set or the RTC clock has failed.
Troubleshooting
Reset the clock in 0-70 Date and Time.
WARNING 201, Fire mode was active
This indicates the frequency converter had entered fire
mode. Cycle power to the unit to remove the warning. See
the fire mode data in the alarm log.
WARNING 202, Fire mode limits exceeded
While operating in fire mode one or more alarm conditions
have been ignored which would normally trip the unit.
Operating in this condition voids unit warranty. Cycle
power to the unit to remove the warning. See the fire
mode data in the alarm log.
WARNING 203, Missing motor
With a frequency converter operating multi-motors, an
under-load condition was detected. This could indicate a
missing motor. Inspect the system for proper operation.
WARNING 204, Locked rotor
With a frequency converter operating multi-motors, an
overload condition was detected. This could indicate a
locked rotor. Inspect the motor for proper operation.
116
Operating Instructions
ALARM 243, Brake IGBT
This alarm is only for enclosure size F frequency converters.
It is equivalent to Alarm 27. The report value in the alarm
log indicates which power module generated the alarm:
ALARM 244, Heat Sink temperature
This alarm is only for enclosure type F frequency
converters. It is equivalent to Alarm 29. The report value in
the alarm log indicates which power module generated
the alarm:
ALARM 245, Heat Sink sensor
This alarm is only for enclosure size F frequency converters.
It is equivalent to Alarm 39. The report value in the alarm
log indicates which power module generated the alarm:
Danfoss A/S © Rev. 06/2014 All rights reserved.
1 = Left most inverter module.
2 = Middle inverter module in enclosure sizes F12
or F3.
2 = Right inverter module in enclosure sizes F10
or F11.
2 = Second frequency converter from the left
inverter module in enclosure size F14.
3 = Right inverter module in enclosure sizes F12
or F13.
3 = Third from the left intverter module in
enclosure size F14.
4 = Far right inverter module in enclosure size
F14.
5 = Rectifier module.
6 = Right rectifier module in enclosure size F14.
1 = Left most inverter module.
2 = Middle inverter module in enclosure size F12
or F3.
2 = Right inverter module in enclosure size F10
or F11.
2 = Second frequency converter from the left
inverter module in enclosure size F14.
3 = Rght inverter module in enclosure sizes F12
or F13.
3 = Tird from the left intverter module in
enclosure size F14.
4 = Far right inverter module in enclosure sizes
F14.
5 = Rectifier module.
6 = Right rectifier module in enclosure sizes F14.
1 = Left most inverter module.
2 = Middle inverter module in enclosure sizes F12
or F13.
2 = Right inverter module in enclosure sizes F10
or F11.