DC braking initiated using a control command
command, e.g. p1230 = 722.3 (control command
DC braking when falling below a starting speed
1. The motor speed has exceeded the starting speed.
2. The inverter activates the DC braking as soon as the motor speed falls below the starting
DC braking when a fault occurs
1. A fault occurs, which initiates DC braking as response.
2. The motor brakes along the down ramp to the speed for the start of DC braking.
3. DC braking starts.
DC braking initiated by a control command
1. The higher-level control issues the command for DC braking, e.g. using DI3: p1230 =
2. DC braking starts.
If the higher-level control withdraws the command during DC braking, the inverter interrupts
DC braking and the motor accelerates to its setpoint.
Converter with control units CU250D-2
Operating Instructions, 04/2014, FW V4.7, A5E34261542B AA
DC braking when falling below a start speed
Precondition: p1230 = 1 and p1231 = 14
Precondition: p1231 = 4 and p1230 = control
via DI 3)
speed.
722.3.
8.8 Application-specific functions
DC braking when a fault occurs
Precondition: Fault number and fault response
are assigned using p2100 and p2101
DC braking when switching off the motor
Precondition: p1231 = 5 or p1230 = 1 and p1231
= 14
Setting functions
225