Setting functions
8.5 Motor control
8.5.2.3

Optimizing the speed controller

Optimum control response - post optimization not required
You do not have to manually adapt the speed controller if, after the speed controller self
optimization, the motor manifests the following acceleration response:
Control optimization required
In some cases, the self optimization result is not satisfactory, or the inverter cancels the self-
optimization routine with a fault. Further, self optimization is not permissible in plants and
systems in which the motor cannot freely rotate.
In these cases you must manually optimize the speed controller.
The examples listed below show you which variables you can use to adapt the control
response.
The basic procedure is described in the following section for STARTER and the operator
panel.
Depending on whether the control operates with or without encoder, different parameters
define the controller response.
Encoderless speed control
Speed control with encoder
142
Optimum control response for applications that do not permit
any overshoot.
The actual value approaches the setpoint without any
significant overshoot.
Optimum control response for fast correction and quick
compensation of noise components.
The actual value approaches the setpoint and slightly
overshoots, maximum 10% of the setpoint step.
K
p
p1470
p1460
Operating Instructions, 04/2014, FW V4.7, A5E34261542B AA
T
n
p1472
p1462
Converter with control units CU250D-2