Activate Settings - Siemens SINAMICS G120D Original Instructions Manual

Cu250d-2 series
Hide thumbs Also See for SINAMICS G120D:
Table of Contents

Advertisement

8.9.3.8

Activate settings

Activate settings
Procedure
To activate the settings for the safety functions, proceed as follows:
1. Press the "Copy parameters" button, to create a redundant image of your inverter
2. Press the "Activate settings" button.
3. If the password is the factory default, you are prompted to change the password.
4. Confirm the prompt for saving your settings (copy RAM to ROM).
5. Switch off the inverter supply voltage.
6. Wait until all LEDs on the inverter go dark (no voltage condition).
7. Switch on the inverter supply voltage again.
Your settings are now active.
Parameter
p9700 = D0 hex
p9701 = DC hex
p0010 = 0
p0971 = 1
Converter with control units CU250D-2
Operating Instructions, 04/2014, FW V4.7, A5E34261542B AA
settings.
If you try to set a password that is not permissible, the old password will not be changed.
Description
SI copy function (factory setting: 0)
Starting the SI parameter copy function.
Confirm data change (factory setting: 0)
Confirm SI basic parameter change.
Drive commissioning parameter filter
0: Ready
Save parameter
1: Save the drive object (copy from RAM to ROM)
After the inverter has saved the parameters in a non-volatile fashion, then
p0971 = 0.
8.9 Safe Torque Off (STO) safety function
Setting functions
247