Electrical Data - Siemens SINAMICS G120D Original Instructions Manual

Cu250d-2 series
Hide thumbs Also See for SINAMICS G120D:
Table of Contents

Advertisement

4.2.2

Electrical data

Power Module specifications - 3AC 380 V ... 500 V ± 10 %
Table 4- 1
Product
6SL3525-...
0PE17-5AA1
0PE21-5AA1
0PE23-0AA1
0PE24-0AA1
0PE25-5AA1
0PE27-5AA1
Standby current
If the converter is powered-up, but the motor is still switched off, the converter requires a
standby current.
You have to consider the standby current when calculating the size of the conductors and
selecting the correct protective devices on the line supply.
Table 4- 2
Converter
0.75 - 1.5 kW
3.0 - 4.0 kW
5.5 - 7.5 kW
For more comprehensive information on the standby current, please read the following FAQ:
Standby currents for PM250D
(http://support.automation.siemens.com/WW/view/en/31764702)
Brake voltage
The brake voltage of 180 V DC is suitable for brakes which require 400 V AC with rectifier.
Remove the rectifier module and connect the brake output of the converter directly to the
brake coil.
The UL approved current rating for the brake output is 600 mA.
Converter with control units CU250D-2
Operating Instructions, 04/2014, FW V4.7, A5E34261542B AA
Rated Output, Input and Fuses
Frame size
Rated output
kW
A
0.75
A
1.5
B
3
C
4
C
5.5
C
7.5
Standby currents of the converter
50 Hz
380 V
400 V
0.6
0.63
2.2
2.32
2.9
3.05
HO
Rated output
Rated input
current
current
A
A
2.2
2.1
4.1
3.8
7.7
7.2
10.2
9.5
13.2
12.2
19
17.7
Standby current (A)
415 V
380 V
0.66
0.7
2.40
2.7
3.15
3.5
Installation
4.2 Electrical Installation
Fuse
3NA3...
A
Type
10
803-
10
803-
16
805-
20
807-
20
807-
32
812-
60 Hz
440 V
480 V
0.8
0.91
3.2
3.33
4.0
4.40
33