Siemens SINAMICS G120D Original Instructions Manual page 321

Cu250d-2 series
Hide thumbs Also See for SINAMICS G120D:
Table of Contents

Advertisement

Number
Cause
F08501
Setpoint timeout
F08502
Monitoring time, sign-of-life expired •
F08510
Send configuration data not valid
A08511
Receive configuration data not
valid
A08526
No cyclic connection
A08565
Consistency error for adjustable
parameters
F08700
Communications error
F13100
Know-how protection: Copy
protection error
F13101
Know-how protection: Copy
protection cannot be activated
Converter with control units CU250D-2
Operating Instructions, 04/2014, FW V4.7, A5E34261542B AA
Remedy
Check the PROFINET connection.
Set the controller to RUN mode.
If the error occurs repeatedly, check the monitoring time set (p2044).
Check the PROFINET connection.
Check the PROFINET configuration
Activate the controller with cyclic operation.
Check the parameters "Name of Station" and "IP of Station" (r61000,
r61001).
Check the following:
IP address, subnet mask or default gateway is not correct.
IP address or station name used twice in the network.
Station name contains invalid characters.
A CAN communications error has occurred. Check the following:
Bus cable.
Baud rate (p8622).
Bit timing (p8623).
Master
Start the CAN controller manually with p8608 = 1 after the cause of the
fault has been resolved!
The know-how protection and the copy protection for the memory card
are active. An error occurred when checking the memory card.
Insert a suitable memory card and switch the converter supply voltage
temporarily off and then on again (POWER ON).
Deactivate the copy protection (p7765).
Insert a valid memory card.
Alarms, faults and system messages
11.6 List of alarms and faults
321