Setting functions
8.8 Application-specific functions
Parameter
p0490
p0580
p0581
p0582
p0583
p0585
r0586
p2181
p2192
p2193 = 2
p3230 = 586
p3231
The "Probe" subfunction calculates the speed from the pulse signal of the digital input.
1)
For more information, see the List Manual (the parameter list and function diagram 8013).
236
Description
Invert probe
(factory setting 0000bin)
1)
Using the 3rd bit of the parameter value, invert the input signals of digital input 3
for the probe.
Probe
Input terminal (factory setting 0)
1)
Connect input of probe with a digital input.
Probe
Edge (factory setting 0)
1)
Edge for analyzing the probe signal for measuring speed list value
0: 0/1 edge
1: 1/0 edge
Probe
Pulse per revolution (factory setting 1)
1)
Number of pulses per revolution
Probe
Maximum measurement time (factory setting 10 s)
1)
Maximum measurement time for the probe If there is no new pulse before the
maximum measuring time elapses, the inverter sets the actual speed value in
r0586 to zero.
The time is restarted with the next pulse.
Probe
Gear ratio (factory setting 1)
1)
The inverter multiplies the measured speed by the gear ratio before displaying it
in r0586.
Probe
Speed list value
1)
Result of the speed calculation
Load monitoring response (factory setting 0)
Response for evaluating load monitoring.
0 Load monitoring disabled
1 A07920 for speed too low
2 A07921 for speed too high
3 A07922 for speed outside tolerance
4 F07923 for speed too low
5 F07924 for speed too high
6 F07925 for speed outside tolerance
Load monitoring delay time (factory setting 10 s)
Delay time for evaluating load monitoring.
Load monitoring configuration (factory setting: 1)
2: Speed deviation and load failure monitoring.
Load monitoring actual speed value (factory setting 0)
Result of the speed calculation with the evaluation of the speed monitoring.
Load monitoring speed deviation (factory setting 150 rpm)
Permissible speed deviation of load monitoring.
Converter with control units CU250D-2
Operating Instructions, 04/2014, FW V4.7, A5E34261542B AA