Alarms, faults and system messages
11.6 List of alarms and faults
Number
Cause
A07455
Maximum velocity limited
A07456
Setpoint velocity limited
A07457
Combination of input signals is not
permissible
F07458
Reference cam not found
F07459
No zero mark available
F07460
End of reference cam not found
A07461
Reference point not set
A07462
Selected traversing block number
does not exist
A07463
External block change not
requested in the traversing block
F07464
Traversing block is inconsistent
316
Remedy
The maximum velocity (p2571) is too high to correctly calculate the
modulo correction. Remedy:
Reduce the maximum velocity (p2571).
Increase the sampling time for positioning (p0115[ 5]).
The actual setpoint velocity is greater than the parameterized maximum
velocity (p2571), and is therefore limited. Remedy:
Check the entered setpoint velocity.
Reduce the velocity override (CI: p2646).
Increase the maximum velocity (p2571).
An illegal combination of input signals, which are simultaneously set was
detected, e.g.:
Jog 1 and jog 2 (p2589, p2590).
Jog 1 or jog 2 and direct setpoint input/MDI (p2589, p2590, p2647).
Jog 1 or jog 2 and start referencing (p2589, p2590, p2595).
Jog 1 or jog 2 and activate traversing task (p2589, p2590, p2631).
Direct setpoint input/MDI and start referencing (p2647, p2595).
Direct setpoint input/MDI and activate traversing task (p2647, p2631).
Start referencing and activate traversing task (p2595, p2631).
After starting the reference point approach, the axis has traversed
through the maximum permissible distance to search for the reference
cam without finding the reference cam. Remedy:
Check the "reference cam" binector input (BI: p2612).
Check the maximum permissible distance to the reference cam
(p2606).
If axis does not have a reference cam, then set p2607 to 0.
After leaving the reference cam, the axis traversed through the maximum
permissible distance between the reference cam and zero mark without
finding the zero mark. Remedy:
Check the encoder regarding the zero mark.
Check the maximum permissible distance between the reference cam
and zero mark (p2609).
Use an external encoder zero mark (p0494).
During the reference point approach, the axis, when approaching the zero
mark, has reached the end of the traversing range without identifying an
edge at the binector input "Reference cam" (BI: p2612). Remedy:
Check the "reference cam" binector input (BI: p2612).
Reference the system
Correct the traversing program.
Resolve the reason why the edge is missing at binector input (BI: p2632).
Check the traversing block and, if necessary, take into consideration any
alarms that are present.
Operating Instructions, 04/2014, FW V4.7, A5E34261542B AA