Sinamics G120D Specifications - Siemens SINAMICS G120D Original Instructions Manual

Cu250d-2 series
Hide thumbs Also See for SINAMICS G120D:
Table of Contents

Advertisement

Technical data

12.3 SINAMICS G120D specifications

12.3
SINAMICS G120D specifications
Power Module Specifications
Note
UL certified Fuses must be used
In order that the system is in compliance with UL requirements, UL listed class H, J or K
fuses, circuit breakers or self-protected combination motor-controllers must be used.
Table 12- 3
Power Module Frame Sizes A and B, 3 AC 380 V ... 500 V, ± 10 %
Order No.
Output Rating (HO)
Output Power
Rated Input Current
HO Output Current
Fuse
Weight (nett)
Weight (packed)
Table 12- 4
Power Module Frame Sizes C, 3 AC 380 V ... 500 V, ± 10 %
Order No.
Output Rating (HO)
Output Power
Rated Input Current
HO Output Current
Fuse
Weight (nett)
Weight (packed)
328
6SL3525 -
0PE17-5AA1
[kW]
[kVA]
[A]
[A]
[A]
[kg]
[lbs]
[kg]
[lbs]
6SL3525 -
0PE24-0AA1
[kW]
[kVA]
[A]
[A]
[A]
[kg]
[lbs]
[kg]
[lbs]
0PE21-5AA1
0.75
2.1
2.2
10
5.5
12.1
12.1
6.5
14.3
14.3
0PE25-5AA1
4
9.5
12.2
10.2
13.2
20
9.5
20.9
20.9
10.5
10.5
23.1
23.1
Operating Instructions, 04/2014, FW V4.7, A5E34261542B AA
0PE23-0AA1
1.5
3.8
7.2
4.1
7.7
10
16
5.5
8.5
18.7
6.5
9.5
20.9
0PE27-5AA1
5.5
7.5
17.7
19
20
32
9.5
9.5
20.9
10.5
23.1
Converter with control units CU250D-2
3

Hide quick links:

Advertisement

Table of Contents
loading