To install the GSDML of the inverter into the configuring tool of your control system, proceed
as follows:
1. Load the GSDML to your PC.
2. Unzip the GSDML file to a folder on your computer.
3. Import the GSDML into the configuring tool of your control system.
You have now installed the GSDML.
7.2.4

Select telegram

PROFIdrive telegrams
If you have not activated the function "Basic positioner" in the inverter, the following
telegrams will be available:
p0922 =
The following values apply if you have enabled the "Basic positioner" function in the inverter:
A more detailed depiction of the individual telegrams can be found in Section Cyclic
communication (Page 94).
Converter with control units CU250D-2
Operating Instructions, 04/2014, FW V4.7, A5E34261542B AA
– On the Internet: GSDML
(http://support.automation.siemens.com/WW/view/en/22339653/133100).
– From your inverter:
Insert a memory card into the converter.
Set p0804 = 12.
The inverter writes the GSDML as zipped file (*.zip) into directory
/SIEMENS/SINAMICS/DATA/CFG on the memory card.
1:
Standard telegram 1, PZD-2/2 (factory setting)
2:
Standard telegram 2, PZD-4/4
3:
Standard telegram 3, PZD-5/9
4:
Standard telegram 4, PZD-6/14
20:
Standard telegram 20, PZD-2/6
350:
SIEMENS telegram 350, PZD-4/4
352:
SIEMENS telegram 352, PZD-6/6
353:
SIEMENS telegram 353, PZD-2/2, PKW-4/4
354:
SIEMENS telegram 354, PZD-6/6, PKW-4/4
999:
Extend telegrams and change signal interconnection (Page 109)
7:
Standard telegram 7, PZD-2/2
9:
Standard telegram 9, PZD-10/5
110:
SIEMENS telegram 110, PZD-12/7
111:
SIEMENS telegram 111, PZD-12/12
999:
Factory setting. See also Extend telegrams and change signal
interconnection (Page 109)