Status Word Messages - Siemens SINAMICS G120D Original Instructions Manual

Cu250d-2 series
Hide thumbs Also See for SINAMICS G120D:
Table of Contents

Advertisement

Configuring the fieldbus
7.4 PROFIdrive profile for PROFIBUS and PROFINET
7.4.1.9

Status word messages

Status word messages (MELDW)
Table 7- 15
Status word for messages and interconnection with parameters in the converter
Bit
Meaning
0
0 = Ramp-function generator active
1 = Ramp-up/ramp-down completed
1
1 = Torque utilization [%] < torque threshold value 2
(p2194)
2
1 = |n_act| < speed threshold value 3 (p2161)
3
1 = |n_act| speed threshold value 2 (p2155)
4, 5
Reserved
6
1 = No motor overtemperature alarm
7
1 = No alarm, thermal power unit overload
8
1 = Speed setpoint - actual value deviation within
tolerance t_on
9, 10
Reserved
11
1 = Controller enable
12
1 = Drive ready
13
1 = Pulses enabled
14, 15
Reserved
108
Description
The motor is presently
accelerating or braking
Speed setpoint and actual
speed are the same.
---
---
---
The motor temperature is
within the permissible range.
The converter temperature is
within the permissible range.
Speed setpoint and actual
speed are within the
permissible tolerance range
p2163.
The speed controller is
enabled.
The converter is ready to be
switched on.
The motor is switched on.
Converter with control units CU250D-2
Operating Instructions, 04/2014, FW V4.7, A5E34261542B AA
P No.
p2082[0] = r2199.5
p2082[1] = r2199.11
p2082[2] = r2199.0
p2082[3] = r2197.1
p2082[6] = r2135.14
p2082[7] = r2135.15
p2082[8] = r2199.4
p2082[11] = r0899.8
p2082[12] = r0899.7
p2082[13] = r0899.11