Heating and Cooling Output (M+M_HTCL_T_)

M+M_HTCL_T_
This FB outputs two manipulated values after split conversion and output conversion to setting values. It can perform
temperature control by outputting the values to both the heating and cooling operation terminal. The primary loop can be
tracked.
FBD/LD
M+M_HTCL_T_
CASIN_T
MVN_HT
MVN_CL
Applicable tag type
HTCL
Control mode
MAN
■Block diagram
MCHG function
(M+P_MCHG) *
CASIN_T
(Tracking)
CAS
SV
* (M+P_ ) indicates the main structure member tag access FB which is the main component of each function.
Setting data
■Input/output variable
Variable
Description
name
CASIN_T
Cascade SV input (unit: %) (With tracking) (Indirect
address)
MVN_HT
Output to a module (heating side)
MVN_CL
Output to a module (cooling side)
12 LOOP TAG
442
12.40 Heating and Cooling Output (M+M_HTCL_T_)
AUT
Variation rate
high/low limiter
Split
conversion
Tracking
(primary loop)
Disable alarm detection
TRK = 1
MAN,
AUT,
CMV
MHA_HT
MLA_HT
DMLA_HT MHA_CL MLA_CL DMLA_CL
CAS
M+M_HTCL_T_
Variation rate
high/low limiter
MV_HT
MV_CL
ALM
Reflect primary
loop AT result
Recommended range
0 to 100[%]
NMIN_HT to NMAX_HT
NMIN_CL to NMAX_CL
CMV
CSV
Tight shut/
MV reverse
full open
Tight shut/
MV reverse
full open
PID tracking
(primary loop)
Tracking
Primary loop tag
parameter
selection
PROPORTIONAL,
processing
INTEGRAL,
DERIVATIVE
PRM_SEL
0
1
P_HT
I_HT
D_HT
2
P_CL
3
Type
Input variable
Output variable
Output variable
MVN_HT
Output
conversion
MVN_CL
Output
conversion
PRM_TRK
I_CL
D_CL
Tag data
Data type
DWORD
REAL
REAL