■Disable alarm detection
This function block sets whether to detect alarms (ALM) or not in the deviation check.
Item
Disable alarm detection by setting tag data
Disable alarm detection by loop stop processing
■Loop stop processing
When the stop alarm (SPA) of the alarm (ALM) is TRUE, this function block performs the following processing.
• MV is cleared to 0.
• The control mode is automatically switched to MANUAL.
• When DVLA of the alarm (ALM) has occurred, the DVLA is reset.
• No alarm is detected in the deviation check.
■Processing operation
: Performed, : Not performed
Control mode
MAN, CMV, AUT
CAS, CSV
*1 An alarm whose corresponding bit is TRUE (Valid) in the disable alarm detection (INH) is not detected.
Operation error
Error code
Description
(SD0)
3400H
An invalid operation (such as division by zero) is performed.
3402H
Input data (PVP), operation constant (MTD, DVLS, PN, SVPTN_B0), or tag data is a subnormal number or NaN (not a number).
3403H
An overflow has occurred.
3405H
The control cycle (CT) setting is less than 0.
The execution cycle (T) setting is less than 0.
The value divided the control cycle (CT) by the execution cycle (T) exceeds 32767.
10 LOOP CONTROL OPERATION
290
10.18 Blend PI Control (Disable Tracking for primary loop) (M+P_BPI)
Processing operation
Deviation check
BPI operation
Disable alarm detection processing
If the following bits in the disable alarm detection (INH) are TRUE, no DVLA of
the alarm (ALM) will be detected.
• ERRI
• DVLI
Page 290 Loop stop processing
Engineering value
Inverse
conversion
engineering value
conversion
Alarm
*1
*1