■PV tracking function
To avoid sudden changes of the manipulated value at mode switching (from MAN to AUT), this function block matches the
setting value (target) with the process variable when the control mode is MAN or CMV and keeps the value.
Condition
When PVTRK_EN is TRUE and the control mode is "MAN (CMV)"
When PVTRK_EN is FALSE and the control mode is other than "MAN (CMV)"
■SV variation rate & high/low limiter
This function block checks the variation rate and high/low limits to the setting value every control cycle (CT).
• Variation rate limiter
When the control mode is AUT, CAS, or CSV
The SV variation rate high limit value input in percentage is converted into an engineering value, and the processing will be
performed.
DSVL  DSVLT (DSVL: SV variation rate high limit value, DSVLT: SV variation rate high limit value converted into an
engineering value)
Condition
|SV - SVC|  DSVLT
SV -SVC > DSVLT
SV - SVC < -DSVLT
SV: Setting value (target), SVC: Setting value (current)
If DSVLI of the disable alarm detection 2 or ERRI of the disable alarm detection is TRUE, DSVLA will be FALSE.
When the control mode is MAN, CMV, or CASDR
Condition
None
• High/low limiter
When the control mode is MAN, AUT, CAS, CMV, or CSV and SVLMT_EN is TRUE
Condition
Variation rate limiter result > SH
Variation rate limiter result < SL
SL  Variation rate limiter result  SH
If SVLI of the disable alarm detection 2 or ERRI of the disable alarm detection is TRUE, SVLA will be FALSE.
If SVHI of the disable alarm detection 2 or ERRI of the disable alarm detection is TRUE, SVHA will be FALSE.
The high/low limiter result is stored in SVC (setting value (current)).
When the control mode is CASDR, or when SVLMT_EN is FALSE
The variation rate limiter result is stored in SVC (set value (current)).
■Integration stop
This function block stops an integral element operation.
Condition
ISTP = TRUE
ISTP = FALSE
10.7 2-degree-of-freedom Advanced PID Control (Enable Tracking for primary loop) (M+P_2PIDH_T_)
Variation rate limiter result
SV
SVC + DSVLT
SVC - DSVLT
Variation rate limiter result
SV
High/low limiter result
SH
SL
Variation rate limiter result
Processing
The integral element operation is stopped.
Non-processing
PV tracking processing
Setting value (target) = Process variable
Setting value (current) = Process variable
Non-processing
Alarm 2 (ALM2) target variation rate limit (DSVLA)
FALSE (Reset)
TRUE (Detected)
TRUE (Detected)
Alarm 2 (ALM2) target variation rate limit (DSVLA)
FALSE (Reset)
Alarm 2 (ALM2)
SV low limit (SVLA)
FALSE (Reset)
TRUE (Detected)
FALSE (Reset)
10 LOOP CONTROL OPERATION
SV high limit (SVHA)
TRUE (Detected)
FALSE (Reset)
FALSE (Reset)
219