Operation error
Error code
Description
(SD0)
3400H
An invalid operation (such as division by zero) is performed.
3402H
Input data (PVP), operation constant (MTD, DVLS, PN, SVPTN_B0), or tag data is a subnormal number or NaN (not a number).
3403H
An overflow has occurred.
3405H
The control cycle (CT) setting is less than 0.
The execution cycle (T) setting is less than 0.
The value divided the control cycle (CT) by the execution cycle (T) exceeds 32767.
The sampling interval time for AT1 (AT1ST) setting is less than 0.
The time-out interval for AT1 (AT1TOUT1) setting is less than 0.
The time-out interval after maximum slope for AT1 (AT1TOUT2) setting is less than 0.
The execution cycle (T) setting is less than 0.
The value divided the sampling interval time for AT1 (AT1ST) by the execution cycle (T) exceeds 32767.
The value divided the time-out interval for AT1 (AT1TOUT1) by the execution cycle (T) exceeds 32767.
The value divided the time-out interval after maximum slope for AT1 (AT1TOUT2) by the execution cycle (T) exceeds 32767.
10.6 2-degree-of-freedom PID Control (Disable Tracking for primary loop) (M+P_2PID)
10 LOOP CONTROL OPERATION
10
213