Ratio Control (Disable Tracking For Primary Loop) (M+P_R) - Mitsubishi Electric MELSEC iQ-R Series Programming Manual

Process control function blocks
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

10.2
Ratio Control (Disable Tracking for primary loop)
(M+P_R)
M+P_R
This FB controls two sets of control amount at a constant ratio and outputs the result (MV).
FBD/LD
M+P_R
PVP
MVP
CASIN
Applicable tag type
R
Control mode
MAN
AUT
■Block diagram
(%)
PVP
Engineering
(%)
CASIN
value
conversion
CAS
Tag data
Setting data
■Input/output variable
Variable
Description
name
PVP
PV input (unit: %)
CASIN
Cascade SV input (unit: %)
MVP
MV output (unit: %)
■Public variable (operation constant)
Variable
Description
name
SVPTN_B0
Setting value (SV) used
■Tag data
For details on tag data that is read or written with this tag access FB, refer to the following.
Page 523 R
CAS
M+P_R
Variation
rate limiter
SPR
Recommended
range
0 to 100[%]
0 to 100[%]
-999999 to 999999[%]
Recommended
range
TRUE: Not used
FALSE: Used

10.2 Ratio Control (Disable Tracking for primary loop) (M+P_R)

CMV
CSV
(%)
MVP
Ratio
operation
Type
Input variable
Input variable
Output variable
Initial value
Set by
TRUE
User
10 LOOP CONTROL OPERATION
10
Data type
REAL
REAL
REAL
Data type
BOOL
187