Mitsubishi Electric MELSEC iQ-R Series Programming Manual page 612

Process control function blocks
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Ex.
When the ranges of PVN and MVN are different (the range of A/D conversion module (AIN_4CH) is 0 to 32000, and the range
of D/A conversion module (AOUT_4CH) is -32000 to 32000)
• Program example for the simulation function (SIMULATION mode)
M+P_ENG and M+P_IENG convert FIC001_FB.SIMOUT into FIC001_FB.SIMIN for connection.
NORMAL
mode
SIMULATION
mode
(1) Analog input module CH1 digital output value
(2) Analog output module CH1 digital value
(3) The engineering value inverse conversion of 0 to 32000/0 to 100 (%)
(4) The engineering value conversion of 0 to 100 (%)/-32000 to 32000
• Program example for the simulation function (SIMULATION mode) (with Primary delay + Dead time)
Convert the range from FIC001_FB.SIMOUT to FIC001_FB.SIMIN by M+P_ENG and M+P_IENG.
NORMAL
mode
SIMULATION
mode
(1) Analog input module CH1 digital output value
(2) Analog output module CH1 digital value
(3) The engineering value inverse conversion of 0 to 32000/0 to 100 (%)
(4) The engineering value conversion of 0 to 100 (%)/-32000 to 32000
APPX
610
Appendix 3 Related Functions of Process
(1)
(3)
(1)
(3)
(4)
(4)
(2)
(2)