Mitsubishi Electric MELSEC iQ-R Series Programming Manual page 296

Process control function blocks
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

■Processing operation
: Performed, : Not performed
Control mode
MAN, CMV, AUT, CAS, CSV, CASDR
*1 An alarm whose corresponding bit is TRUE (Valid) in the disable alarm detection (INH) is not detected.
Operation error
Error code
Description
(SD0)
3400H
An invalid operation (such as division by zero) is performed.
3402H
Input data (PVPI) or tag data is a subnormal number or NaN (not a number).
3403H
An overflow has occurred.
3405H
The variation rate alarm value (DPL) is less than the variation rate alarm value (DPL) in negative.
The execution cycle (T) setting is less than 0.
The variation rate alarm check time (CTIM) setting is less than 0.
The value divided the variation rate alarm check time (CTIM) by the execution cycle (T) exceeds 32767.
10 LOOP CONTROL OPERATION
294
10.19 High/Low Limit Alarm Check (M+P_PHPL)
Processing operation
High high limit/high limit/low limit/low
low limit check
Variation rate
Engineering
check
value
conversion
Alarm
*1