Mitsubishi Electric MELSEC iQ-R Series Programming Manual page 329

Process control function blocks
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

■Public variable (operation constant)
Variable
Description
name
NMAX
Output Conversion High Limit
NMIN
Output Conversion Low Limit
TRK
Tracking Flag
SVPTN_B4
CASIN_T Pattern
■Tag data
For details on tag data that is read or written with this tag access FB, refer to the following.
Page 544 SEL
Processing details
■Input selection processing
Selection signal (SELECT)
FALSE
TRUE
■Variation rate & high/low limiter
This function block checks the variation rate and high/low limits of the input value.
• Variation rate limiter
DML
DML
Execution cycle(ΔT)
Condition
|T - MV|  DML
T - MV > DML
T - MV < -DML
T: Tentative manipulated value, MV: Manipulated value, DML: Output variation rate high limit value
Recommended
range
-999999 to 999999
-999999 to 999999
0: Not executed
1: Executed
TRUE: Not primary MV
FALSE: Primary MV
Result
The input PVP (%) is selected.
The input CASIN_T (%) is selected.
Tentative MV value (T)
DML
DML
Variation rate limiter processing result
T
MV + DML
MV - DML
10.27 Loop Selector (Enable Tracking for primary loop only by CASIN_T) (M+P_SEL_T1)
Initial value
100.0
0.0
0
TRUE
Variation rate limiter
processing value
DML
DML
DML
t
Alarm (ALM)
Output variation rate limit (DMLA)
FALSE (Reset)
TRUE (Detected)
TRUE (Detected)
10 LOOP CONTROL OPERATION
Set by
Data type
User
REAL
User
REAL
User
INT
User
BOOL
327