Mitsubishi Electric MELSEC iQ-R Series Programming Manual page 273

Process control function blocks
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

■Public variable (operation constant)
Variable
Description
name
MTD
Derivative Gain
DVLS
Large Deviation Alarm Hysteresis
PN
Reverse Action/Direct Action
*1
TRK
Tracking Flag
SVPTN_B0
Setting Value (SV) Used
SVPTN_B1
Setting Value (SV) Pattern
*1 When 1 (tracking is executed) is set to the tracking flag, connect CASOUT_T of the primary loop with the input variable CASIN_T.
■Tag data
For details on tag data that is read or written with this tag access FB, refer to the following.
Page 515 IPD
Processing details
■Deviation check
This function block performs deviation check processing.
DVL
0
-DVL
DVLA
occur
Condition
DVL < |DV|
|DV|  (DVL - DVLS)
DV: Deviation (%), DVLS: Large deviation alarm hysteresis (%), DVL: Deviation limit value (%)
Recommended range
0 to 9999
0 to 100
0: Reverse action
1: Direct action
0: Not executed
1: Executed
TRUE: Not used
FALSE: Used
TRUE: Not primary MV
FALSE: Primary MV
DVLA
DVLA
DVLA
reset
occur
reset
10.15 I-PD Control (Enable Tracking for primary loop) (M+P_IPD_T)
Initial value
8.0
2.0
0
0
TRUE
TRUE
DVLS
t
DVLS
Alarm (ALM)
Large deviation (DVLA)
TRUE (Detected)
FALSE (Reset)
10 LOOP CONTROL OPERATION
Set by
Data type
User
REAL
User
REAL
User
INT
User
INT
User
BOOL
User
BOOL
271
10