Mitsubishi Electric MELSEC iQ-R Series Programming Manual page 169

Process control function blocks
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Setting data
■Input/output variable
Variable
Description
name
MVN
Output to a module
■Public variable (operation constant)
Variable
Description
name
NMAX
Output Conversion High Limit
NMIN
Output Conversion Low Limit
■Tag data
For details on tag data that is read or written with this tag access FB, refer to the following.
Page 490 Tag Data List
Processing details
■Output conversion
This function block performs output conversion processing.
Output of output conversion (MVN)
NMAX
NMIN
(-10(%))
0(%)
Converted output (MVN)={(NMAX-NMIN)×
NMAX: Output conversion high limit value
NMIN: Output conversion low limit value
MV: Manipulated variable (%)
MVN: Output conversion output value
■Processing operation
: Performed, : Not performed
Control mode
MAN, CMV
AUT, CAS, CSV
Operation error
Error code
Description
(SD0)
3400H
An invalid operation (such as division by zero) is performed.
3402H
Operation constant (NMAX, NMIN) or tag data is a subnormal number or NaN (not a number).
3403H
An overflow has occurred.
100(%)
(110(%))
MV
}+NMIN
100
Recommended
Type
range
NMIN to NMAX
Output variable
Recommended
Initial value
range
-999999 to 999999
100.0
-999999 to 999999
0.0
Manipulated
variable (MV)
Processing operation
Output conversion
9.5 Manual Output (M+P_MOUT)
Data type
REAL
Set by
Data type
User
REAL
User
REAL
9 I/O CONTROL
167
9

Advertisement

Table of Contents
loading

Table of Contents