Mitsubishi Electric MELSEC iQ-R Series Programming Manual page 364

Process control function blocks
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Variable name
LLAG_EN
LLAG_T1
PVCMP_EN
PVCMP_MODE
PVDCMP_EN
PID2H_MTD
PID2H_DVLS
PID2H_PN
PID2H_TRK
PID2H_SVPTN_B0
PID2H_SVPTN_B1
PID2H_PVTRK_EN
PID2H_ISTP
PID2H_DSTP
PID2H_LMT_ISTP
PID2H_SVLMT_EN
MVDCMP_EN
MVDCMP_MODE
MVDGAINCMP_EN
OUT3_NMAX
OUT3_NMIN
OUT3_MVCMP_EN
OUT3_MVCMP_MODE
OUT3_PREMV_EN
OUT3_PREMV_V
OUT3_MVHLD_EN
OUT3_MVTRK_EN
OUT3_STP_OTYPE
OUT3_SEA_OTYPE
OUT3_ARW_EX_EN
OUT3_MVPH
OUT3_MVPL
12 LOOP TAG
362
12.9 2-degree-of-freedom Advanced PID Control (Enable Tracking for primary loop) (M+M_2PIDH_T_)
Description
First Order Lag: Execution condition
First Order Lag: Delay Time (Sec)
PV Compensation Execution condition
PV Compensation Mode
PV Compensation Execution condition
Derivative Gain
Large Deviation Alarm Hysteresis
Reverse Action/Direct Action
*1
Tracking Flag
Setting Value (SV) Used
Setting Value (SV) Pattern
PV Tracking Execution condition
Integration Stop Signal
Derivation Stop Signal
Stop Integration, when MV variation rate limiter
alarm occurred
SV High/Low Limiter
MV Compensation Execution condition
MV Compensation Mode
MV Gain Correction Execution condition
Output Conversion High Limit
Output Conversion Low Limit
MV Compensation Execution condition
MV Compensation Mode
Preset MV Execution condition
Preset MV Value (Unit: %)
MV Hold Execution condition
MV Tracking Execution condition
Output when loop or tag is stopped
MV Output Selection when SEA is occurred
MV Value Instantaneous Pullback
MV Internal Operation High Limit Value (Unit: %)
MV Internal Operation Low Limit Value (Unit: %)
Recommended range
Initial
value
TRUE: Execute
FALSE
FALSE: Stop
0 to 999999[s]
1.0
TRUE: Execute
FALSE
FALSE: Stop
0: Addition
0
1: Replacement
TRUE: Execute
FALSE
FALSE: Stop
0 to 9999
8.0
0 to 100
2.0
0: Reverse action
0
1: Direct action
0: Not executed
0
1: Executed
TRUE: Not used
TRUE
FALSE: Used
TRUE: Not primary MV
TRUE
FALSE: Primary MV
TRUE: Execute
FALSE
FALSE: Stop
TRUE: Execute
FALSE
FALSE: Stop
TRUE: Execute
FALSE
FALSE: Stop
TRUE: Stop
FALSE
FALSE: Not stop
TRUE: Execute
FALSE
FALSE: Not execute
TRUE: Execute
FALSE
FALSE: Stop
0: Addition
0
1: Replacement
TRUE: Execute
FALSE
FALSE: Stop
-999999 to 999999
100.0
-999999 to 999999
0.0
TRUE: Execute
FALSE
FALSE: Stop
0: Addition
0
1: Replacement
TRUE: Execute
FALSE
FALSE: Stop
0 to 100[%]
0.0
TRUE: Execute
FALSE
FALSE: Stop
TRUE: Execute
FALSE
FALSE: Stop
0: Hold
0
1: Preset value
0: Hold
0
1: Preset MV output
2: Neither hold nor preset MV
output is performed.
TRUE: Execute
FALSE
FALSE: Not execute
MH to 999999[%]
100.0
-999999 to ML[%]
0.0
Set by
Data type
User
BOOL
User
REAL
User
BOOL
User
INT
User
BOOL
User
REAL
User
REAL
User
INT
User
INT
User
BOOL
User
BOOL
User
BOOL
User
BOOL
User
BOOL
User
BOOL
User
BOOL
User
BOOL
User
INT
User
BOOL
User
REAL
User
REAL
User
BOOL
User
INT
User
BOOL
User
REAL
User
BOOL
User
BOOL
User
INT
User
INT
User
BOOL
User
REAL
User
REAL