Mitsubishi Electric MELSEC iQ-R Series Programming Manual page 47

Process control function blocks
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Correction Operation
The following FBs perform operation processing such as broken line correction, standard filter, engineering value conversion,
temperature/pressure correction, and summation.
■Function Generator
Function block symbol
Processing details
M+P_FG
Outputs (OUT_) values according to the function generator pattern that consists of SN break points
with regard to the input (IN).
■Inverse Function Generator
Function block symbol
Processing details
M+P_IFG
Outputs (OUT_) values according to the function generator pattern that consists of SN break points
with regard to the input (IN).
■Standard Filter (moving average)
Function block symbol
Processing details
M+P_FLT
Outputs (OUT_) the average value of SN pieces of data of the input (IN) collected the at data
collection interval ST.
■Engineering Value Conversion
Function block symbol
Processing details
M+P_ENG
Converts a value (%) of the input (IN) in percentage into an engineering value such as temperature
and pressure and outputs (OUT_) the result.
■Engineering Value Inverse Conversion
Function block symbol
Processing details
M+P_IENG
Converts an input engineering value (IN) such as temperature and pressure into a value in
percentage (%) and outputs (OUT_) the result.
■Temperature/Pressure Correction
Function block symbol
Processing details
M+P_TPC
Executes temperature/pressure correction (or either of temperature correction or pressure
correction) to the input (IN) of the differential pressure (%) and outputs (OUT_) the result.
■Summation
Function block symbol
Processing details
M+P_SUM
When the integration start signal (START) is TRUE, this function block performs integration
processing to the input (IN) and outputs (OUT_) the result.
■Summation (Internal Integer Integration)
Function block symbol
Processing details
M+P_SUM2_
When the integration start signal (START) is TRUE, this function block performs integration
processing to the input (IN) and outputs the result.
Internal integration for the integral part is executed with signed 32-bit integers.
■Range Conversion
Function block symbol
Processing details
M+P_RANGE_
Executes range conversion to the input (IN) and outputs (OUT_) the result.
3 LISTS OF PROCESS CONTROL FUNCTION BLOCK
3.1 General Process FBs
Reference
Page 70 M+P_FG
3
Reference
Page 73 M+P_IFG
Reference
Page 76 M+P_FLT
Reference
Page 78 M+P_ENG
Reference
Page 80 M+P_IENG
Reference
Page 82 M+P_TPC
Reference
Page 84 M+P_SUM
Reference
Page 86 M+P_SUM2_
Reference
Page 89
M+P_RANGE_
45

Advertisement