8.2
Integration (M+P_I)
M+P_I
When the operation signal (INVLD) is FALSE, this function block performs integral operation to the input (IN) and outputs
(OUT_) the result.
FBD/LD
M+P_I
INVLD
OUT_
IN
■Block diagram
Operation signal
INVLD
TRUE: Invalid
FALSE: Valid
IN
Setting data
■Input/output variable
Variable
Description
name
INVLD
Operation signal
IN
Input
OUT_
Output
■Public variable (operation constant)
Variable
Description
name
T_
Integral Time
Ys
Initial Output Value
8 CONTROL OPERATION
114
8.2 Integration (M+P_I)
M+P_I
Integral control
action processing
OUT_
Recommended
range
TRUE: Invalid
FALSE: Valid
-999999 to 999999
-999999 to 999999
Recommended
range
0 to 999999[s]
-999999 to 999999
Type
Data type
Input variable
BOOL
Input variable
REAL
Output variable
REAL
Initial value
Set by
1.0
User
0.0
User
Data type
REAL
REAL