Mitsubishi Electric MELSEC iQ-R Series Programming Manual page 476

Process control function blocks
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

■Count processing
Count RUN status
RESET/START
(1)
RUN
STOP
Count stop status
(1)
When the setting is performed with the faceplate or the value of the input variable (RUN) is changed from FALSE to TRUE, this function block stores the
current value + 1 (counter value) in the process variable (PV) in the unit set with the counter multiplying factor (MULT).
When the process variable (PV) reaches the estimated value (PSV), TRUE will be output from the output variable PRE_COMP. (Preset value comparison
in the block diagram)
When the process variable (PV) reaches the setting value (SV), TRUE will be output from the output variable COMP_, the counter stops, and the status of
the count processing becomes the count stop status. (Setting value comparison in the block diagram)
When the process variable (PV) reaches the counter high limit (RH), the counter stops.
(2)
When the setting is performed with the faceplate or the value of the input variable (STP) is changed from FALSE to TRUE, measuring the process variable
(PV) will be stopped.
(3)
When the setting is performed with the faceplate or the value of the input variable (RST_) is changed from FALSE to TRUE, the process variable (PV) will
be set to the counter low limit (RL) value, and the counter stops.
(4)
When the setting is performed with the faceplate or the value of the input variable (RS_START) is changed from FALSE to TRUE, the process variable
(PV) will be set to the counter low limit (RL) value, and the counter starts.
Operation error
There is no operation error.
13 STATUS TAG
474
13.7 Counter 1 (Counter stops when COMPLETE flag is ON) (M+M_COUNTER1)
(4)
RESET
Count initialization
(2)
(count value → low value)
(3)
RESET
(3)