Processing details
■Temperature/pressure correction processing
This function block executes temperature/pressure correction (or either of temperature correction or pressure correction) to
the differential pressure (%) value input from the input variable IN and outputs the result from the output variable OUT_.
Temperature/pressure correction selection
Temperature correction
Pressure correction
(T_)
(P_)
TRUE
TRUE
FALSE
TRUE
TRUE
FALSE
T_: Temperature correction selection
P_: Pressure correction selection
IN: Differential pressure input (%)
PVTEMP: Measured temperature (engineering value)
PVPRES: Measured pressure (engineering value)
TEMP: Design temperature T' (engineering value)
PRES: Design pressure P' (engineering value)
B1_: Bias temperature (engineering value)
B2_: Bias pressure (engineering value)
OUT_: Output (%)
Always input engineering values to the measured temperature (PVTEMP) and the measured pressure
(PVPRES).
Operation error
Error code
Description
(SD0)
3400H
An invalid operation (such as division by zero) is performed.
3402H
Input data (IN, PVTEMP, PVPRES) or operation constant (TEMP, B1_, PRES, B2_) is a subnormal number or NaN (not a number).
3403H
An overflow has occurred.
A1
A2
TEMP+B1_
PVPRES+B2_
PVTEMP+B1_
PRES+B2_
1.0
PVPRES+B2_
PRES+B2_
1.0
TEMP+B1_
PVTEMP+B1_
5.6 Temperature/Pressure Correction (M+P_TPC)
Output (OUT_)
OUT_ = IN  A1  A2
5 CORRECTION OPERATION
5
83