■When multiple M+M_PGS2_ function blocks are connected (When a program with 32 steps or
more is used)
Set the following items.
Target FB
Type/pin
Lead FB
Public variable
Input pin
Output pin
Following FB
Public variable
Input pin
Output pin
Last FB
Public variable
Input pin
Output pin
• Operation description
PGS001 (first program setter FB) is started in the AUT mode, and the output pin PTNEND turns on for one cycle at
completion.
When PGS002 (second program setter FB) receives the PTNEND output of PGS001, the mode is changed to the AUT mode
by the INITSTART command and the control is switched.
For details, refer to the following.
Page 312 M+P_PGS2_
Variable name
Description
PGS2_PRIMARY
Lead FB specified
LINKIN
Link input
PTNEND
Pattern end output
LINKOUT
Link output
PGS2_PRIMARY
Lead FB specified
INITSTART
Initial start command
LINKIN
Link input
PTNEND
Pattern end output
LINKOUT
Link output
PGS2_PRIMARY
Lead FB specified
INITSTART
Initial start command
LINKIN
Link input
CASOUT
Cascade output (Unit: %)
Setting/connection method
TRUE
Not connected.
Connected with INITSTART of the following FB.
Connected with LINKIN of the following FB.
FALSE
Connected with PTNEND of the preceding FB.
Connected with LINKOUT of the preceding FB.
Connected with INITSTART of the following FB.
Connected with LINKIN of the following FB.
FALSE
Connected with PTNEND of the preceding FB.
Connected with LINKOUT of the preceding FB.
Connected with CASIN of the following tag FB such as
PID.
12.37 Multi-Point Program Setter (M+M_PGS2_)