Mitsubishi Electric MELSEC iQ-R Series Programming Manual page 363

Process control function blocks
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Setting data
■Input/output variable
Variable name
Description
PVN
Input from a module
CASIN_T
Primary loop SV input (Unit: %) (With tracking)
(Indirect address)
PV_CMPIN
PV compensation value
PV compensation value
PVD_CMPIN
MV compensation value (Unit: %)
MVD_CMPIN
MV correction gain value
MVD_GAININ
MV_CMPIN
MV compensation value (Unit: %)
MV_TRKIN
MV tracking input (Unit: %)
MVN
Output to a module
CASOUT
Cascade MV output (Unit: %)
CASOUT_T
Cascade MV output (Unit: %) (With tracking)
(Indirect address)
PV_CMPOUT
Output for PV compensation
Output for MV compensation (Unit: %)
MVD_CMPOUT
MV_CMPOUT
Output for MV compensation (Unit: %)
■Public variable (operation constant)
Variable name
Description
IN_NMAX
Input High Limit
IN_NMIN
Input Low Limit
IN_HH
High Limit Range Error
IN_H
High Limit Range Error Reset
IN_L
Low Limit Range Error Reset
IN_LL
Low Limit Range Error
TPC_SQR
Temperature Pressure Correction pattern
TPC_PVTEMP
Temperature Pressure Correction: Measured
Temperature (Engineering Value)
TPC_PVPRES
Temperature Pressure Correction: Measured
Pressure (Engineering Value)
TPC_TEMP
Temperature Pressure Correction: Design
Temperature
TPC_B1
Temperature Pressure Correction: Bias
Temperature
TPC_PRES
Temperature Pressure Correction: Design
Pressure
TPC_B2
Temperature Pressure Correction: Bias Pressure
SQR_OLC
Square Root Extraction: Output Low Cut-off Value
SQR_K
Square Root Extraction: Coefficient
SQR_DENSITY
Square Root Extraction: Density Correction Value
FG_SN
Function Generator: Number of Points
FG_X1 to FG_X48
Function Generator: Input coordinate (x-
coordinate)
FG_Y1 to FG_Y48
Function Generator: Output coordinate (y-
coordinate)
12.9 2-degree-of-freedom Advanced PID Control (Enable Tracking for primary loop) (M+M_2PIDH_T_)
Recommended range
Type
-999999 to 999999
Input variable
0 to 100[%]
Input variable
-999999 to 999999
Input variable
-999999 to 999999
Input variable
-100 to 100[%]
Input variable
-999999 to 999999
Input variable
-999999 to 999999[%]
Input variable
0 to 100[%]
Input variable
OUT3_NMIN to
Output variable
OUT3_NMAX
0 to 100[%]
Output variable
0 to 100[%]
Output variable
-999999 to 999999
Output variable
-100 to 100[%]
Output variable
0 to 100[%]
Output variable
Recommended range
Initial
value
-999999 to 999999
100.0
-999999 to 999999
0.0
-999999 to 999999
102.0
-999999 to 999999
100.0
-999999 to 999999
0.0
-999999 to 999999
-2.0
0: None
0
1: Square root extraction
2: Temperature correction +
Square root extraction
3: Pressure correction +
Square root extraction
4: Temperature/pressure
correction + Square root
extraction
-999999 to 999999
0.0
-999999 to 999999
0.0
-999999 to 999999
0.0
-999999 to 999999
273.15
-999999 to 999999
0.0
-999999 to 999999
10332.0
0 to 999999
0.0
0 to 999999
10.0
0 to 999999
1.0
0 to 48
0
-999999 to 999999
0.0
-999999 to 999999
0.0
Data type
REAL
DWORD
REAL
REAL
REAL
REAL
REAL
12
REAL
REAL
REAL
DWORD
REAL
REAL
REAL
Set by
Data type
User
REAL
User
REAL
User
REAL
User
REAL
User
REAL
User
REAL
User
INT
User
REAL
User
REAL
User
REAL
User
REAL
User
REAL
User
REAL
User
REAL
User
REAL
User
REAL
User
INT
User
REAL
User
REAL
12 LOOP TAG
361