Batch Counter (M+P_Bc) - Mitsubishi Electric MELSEC iQ-R Series Programming Manual

Process control function blocks
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

9.8

Batch Counter (M+P_BC)

M+P_BC
This function block compares the input (CIN) with the estimated value 1 and estimated value 2, and outputs a completion
signal when the input reaches an estimated value.
At this time, this function block performs the high limit check, variation rate check, and output conversion processing to the
input (CIN).
FBD/LD
M+P_BC
CIN
COMP1
COMP2
Applicable tag type
BC
Control mode
MAN
■Block diagram
CIN
(Count value)
*
Indicates bits item.
Setting data
■Input/output variable
Variable
Description
name
CIN
Count value
COMP1
Setting value 1 (SV1) completed output
COMP2
Setting value 2 (SV2) completed output
■Tag data
For details on tag data that is read or written with this tag access FB, refer to the following.
Page 541 BC
9 I/O CONTROL
176
9.8 Batch Counter (M+P_BC)
AUT
CAS
High limit
check
Disable alarm detection
Tag data
PHA(*)
ALM
CMV
M+P_BC
Variation
Output
rate check
conversion
DPPA(*)
SV1
ALM
Recommended
range
0 to 99999999
TRUE: ON
FALSE: OFF
TRUE: ON
FALSE: OFF
CSV
COMP1
(Output in bit)
COMP2
(Output in bit)
SV2
Type
Input variable
Output variable
Output variable
Data type
DINT
BOOL
BOOL