Advertisement

5.7

Summation (M+P_SUM)

M+P_SUM
When the integration start signal (START) is TRUE, this function block performs integration processing to the input (IN) and
outputs (OUT_) the result.
Use M+P_SUM2_ to reduce the influence of information loss in the single-precision floating-point operation.
( Page 86 M+P_SUM2_)
M+P_SUM is used to keep the compatibility with existing programs.
FBD/LD
M+P_SUM
START
OUT_
IN
■Block diagram
Integration start signal
START
TRUE: Start
FALSE: Stop
IN
Setting data
■Input/output variable
Variable
Description
name
START
Integration start signal
IN
Input
OUT_
Output
■Public variable (operation constant)
Variable
Description
name
ILC
Input Low Cut-off Value
A_
Initial value
RANGE
Input Range
5 CORRECTION OPERATION
84
5.7 Summation (M+P_SUM)
M+P_SUM
Analog integratiion
processing
OUT_
Recommended
range
TRUE: Start
FALSE: Stop
-999999 to 999999
-999999 to 999999
Recommended
range
-999999 to 999999
-999999 to 999999
1 to 3
1: /s
2: /min
3: /hour
Type
Data type
Input variable
BOOL
Input variable
REAL
Output variable
REAL
Initial value
Set by
0.0
User
0.0
User
1
User
Data type
REAL
REAL
INT