Mitsubishi Electric MELSEC iQ-R Series Programming Manual page 259

Process control function blocks
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

■Output conversion
This function block performs output conversion processing.
Converted output (MVN)
NMAX
NMIN
(-10(%))
0(%)
Converted output (MVN)
={(NMAX-NMIN)×
NMAX: Output conversion high limit value
NMIN: Output conversion low limit
MV: Manipulated value (%)
MVN: Output conversion output value
■Disable alarm detection
This function sets whether to detect alarms (ALM) or not in the deviation check and variation rate & high/low limiter
processing.
Item
Disable alarm detection by setting tag data
Disable alarm detection by control mode selection
Disable alarm detection by loop stop processing
■Loop stop processing
When the stop alarm (SPA) of the alarm (ALM) is TRUE, this function block performs the following processing.
• Outputs (MVN) are held.
• The control mode is automatically switched to MANUAL.
• When DVLA, DMLA, MHA, or MLA of the alarm (ALM) has occurred, the DVLA, DMLA, MHA, or MLA is reset.
• No alarm is detected in the variation rate & high/low limiter processing.
■Processing operation
: Performed, : Not performed
Control mode
Processing operation
Deviation
check
MAN, CMV
AUT
CAS, CSV
*1 An alarm (ALM) whose corresponding bit is TRUE (detected) is reset, and the alarm will not be detected.
*2 An alarm whose corresponding bit is TRUE (Valid) in the disable alarm detection (INH) is not detected.
10.12 Position Type PID Control (Disable Tracking for primary loop/Enable Tracking from secondary loop) (M+P_PIDP_EX_)
100(%)
(110(%))
MV
}+NMIN
100
PIDP
Engineering
operation
value
conversion
Manipulated variable (MV)
Disable alarm detection processing
If the following bits in the disable alarm detection (INH) are TRUE, DVLA,
DMLA, MHA, or MLA of the alarm (ALM) will not be detected.
• ERRI
• DVLI
• DMLI
• MHI
• MLI
In the MAN or CMV mode, DVLA, DMLA, MHA, and MLA of the alarm (ALM)
are reset and the DVLA, DMLA, MHA, or MLA will not be detected.
Page 257 Loop stop processing
Inverse
Variation rate
engineering
& high/low
value
limiter
conversion
10 LOOP CONTROL OPERATION
Output
Alarm
conversion
*1
*2
*2
257
10

Advertisement

Table of Contents
loading

Table of Contents