Mitsubishi Electric MELSEC iQ-R Series Programming Manual page 459

Process control function blocks
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Setting data
■Input/output variable
Variable
Description
name
FWD_SET
External input of FWD (forward rotation)
STOP_SET
External input for STOP operation
REV_SET
External input of REV (reverse rotation)
TO_RST
Time-out error external reset input
FWD_ST
Status answer input
REV_ST
Status answer input
TRIP
External failure (TRIP) input
LOCAL
Local operation selection signal
REMOTE
Remote operation selection signal
FWD
ON output for command pulse period
STOP_
ON output for command pulse period
REV
ON output for command pulse period
*1 The default value is FALSE.
■Public variable (others)
• Control mode change processing (MCHG function)
Variable
Description
name
MODEIN
Mode Change Signal
E_
Enable Mode Change
*1 Read or write the variables using a program. They are not displayed on "FB Property" of the engineering tool.
■Tag data
For details on tag data that is read or written with this tag FB, refer to the following.
Page 561 REV
Recommended range
TRUE, FALSE
FALSE  TRUE: FWD
TRUE, FALSE
FALSE  TRUE: STOP
TRUE, FALSE
FALSE  TRUE: REV
TRUE, FALSE
FALSE  TRUE: Time-out reset
TRUE: FWD
FALSE: STOP
TRUE: REV
FALSE: STOP
TRUE: Detected
FALSE: Reset
TRUE: Valid
FALSE: Invalid
TRUE: Valid
FALSE: Invalid
TRUE: Run
FALSE: 
TRUE: Run
FALSE: 
TRUE: Run
FALSE: 
*1
Recommended range
1, 2
1: MAN
2: AUT
TRUE: Execute
FALSE: Stop
Type
*1
Input variable
*1
Input variable
*1
Input variable
*1
Input variable
Input variable
*1
Input variable
*1
Input variable
*1
Input variable
*1
Input variable
*1
Output variable
*1
Output variable
*1
Output variable
*1
Initial value Set by
0
FALSE
13.2 Motor Reversible (2 Input/3 Output) (M+M_REV)
Data type
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
Data type
User
INT
User
BOOL
13 STATUS TAG
457
13