Loop Selector (Enable Tracking For Primary Loop Only By Casin_T) (M+M_Sel_T1) - Mitsubishi Electric MELSEC iQ-R Series Programming Manual

Process control function blocks
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

12.32
Loop Selector (Enable Tracking for primary loop
only by CASIN_T) (M+M_SEL_T1)
M+M_SEL_T1
This FB performs loop selector combining the functions of M+P_SEL_T1 into a single FB. The input 1 is not tracked. The
primary loop of the input 2 is tracked, but tracking from the secondary loop is not performed.
FBD/LD
M+M_SEL_T1
PVP
MVN
CASIN_T
CASOUT
SELECT
Applicable tag type
SEL
Control mode
MAN
■Block diagram
MCHG function
(M+P_MCHG)*
PVP
(%)
CASIN_T
(%)
(Tracking)
SELECT
* (M+P_ ) indicates the main structure member tag access FB which is the main component of each function.
Setting data
■Input/output variable
Variable name
Description
PVP
PV input (Unit: %)
CASIN_T
PV input (Unit: %) (With tracking) (Indirect address)
SELECT
Selection signal
MVN
Output to a module
CASOUT
Cascade output (Unit: %)
*1 Connect CASOUT_T of the primary loop with the input variable CASIN_T.
12 LOOP TAG
418

12.32 Loop Selector (Enable Tracking for primary loop only by CASIN_T) (M+M_SEL_T1)

AUT
CAS
CMV
M+M_SEL_T1
SEL function
(M+P_SEL_T1)*
Recommended range
0 to 100[%]
*1
0 to 100[%]
TRUE: CASIN_T
FALSE: PVP
SEL_NMIN to SEL_NMAX
0 to 100[%]
CSV
(MV output)
(%)
CASOUT
Type
Data type
Input variable
REAL
Input variable
DWORD
Input variable
BOOL
Output variable
REAL
Output variable
REAL
MVN