Mitsubishi Electric MELSEC iQ-R Series Programming Manual page 155

Process control function blocks
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

■Disable alarm detection
This function block sets whether to detect alarms (ALM) or not in the variation rate & high/low limiter processing.
Item
Disable alarm detection by setting tag data
Disable alarm detection by control mode selection
Disable alarm detection by loop stop processing
■Hold processing
This function block sets whether to hold M+P_OUT1 outputs or not when a sensor error (SEA) has occurred in M+P_IN, a tag
access FB.
The hold processing is set in the process control extended setting in the engineering tool.
[Options]  [Convert]  [Process Control Extension Setting]  [I/O Control]  [Holding Processing]
• "Yes" is selected for "Hold the output of M+P_OUT1, M+P_OUT2, M+P_DUTY"; Outputs are held.
• "No" is selected for "Hold the output of M+P_OUT1, M+P_OUT2, M+P_DUTY"; The operation continues.
■Loop stop processing
When the stop alarm (SPA) of the alarm (ALM) is TRUE, this function block performs the following processing.
• Outputs (MVN) are held.
• The control mode is automatically switched to MANUAL.
• When DMLA, MHA, or MLA of the alarm (ALM) has occurred, the DMLA, MHA, or MLA is reset.
• No alarm is detected in the variation rate & high/low limiter processing.
■Processing operation
: Performed, : Not performed
Control mode
Processing operation
Input addition
MAN, CMV
AUT, CAS, CSV
*1 An alarm (ALM) whose corresponding bit is TRUE (detected) is reset, and the alarm will not be detected.
*2 An alarm whose corresponding bit is TRUE (Valid) in the disable alarm detection (INH) is not detected.
Operation error
Error code
Description
(SD0)
3400H
An invalid operation (such as division by zero) is performed.
3402H
Input data (MVD), operation constant (NMAX, NMIN) or tag data memory is a subnormal number or NaN (not a number).
3403H
An overflow has occurred.
Disable alarm detection processing
If the following bits in the disable alarm detection (INH) are TRUE, no DMLA,
MHA, or MLA of the alarm (ALM) will be detected.
• ERRI
• DMLI
• MHI
• MLI
In MAN or CMV mode, DMLA, MHA, and MLA of the alarm (ALM) are reset
and DMLA, MHA, or MLA will not be detected.
Page 153 Loop stop processing
Variation rate &
Reset windup
high/low limiter
9.2 Output Processing-1 with Mode Switching (With Input Addition) (M+P_OUT1)
Output conversion
Alarm
*1
*2
9 I/O CONTROL
9
153

Advertisement

Table of Contents
loading

Table of Contents