High/Low Limiter (M+P_Limt) - Mitsubishi Electric MELSEC iQ-R Series Programming Manual

Process control function blocks
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

8.5

High/Low Limiter (M+P_LIMT)

M+P_LIMT
This FB applies high/low limiters with hysteresis to the input (IN) and outputs (OUT_) the result.
FBD/LD
M+P_LIMT
IN
OUT_
H_
L_
■Block diagram
IN
Setting data
■Input/output variable
Variable
Description
name
IN
Input
OUT_
Output
H_
High limit over detection
L_
Low limit over detection
■Public variable (operation constant)
Variable
Description
name
HILMT
High Limit Value
LOLMT
Low Limit Value
HS1
High Limit Hysteresis
HS2
Low Limit Hysteresis
8 CONTROL OPERATION
122
8.5 High/Low Limiter (M+P_LIMT)
M+P_LIMT
High/low limiter
processing
OUT_
H_
L_
Recommended
range
-999999 to 999999
-999999 to 999999
TRUE: Detected
FALSE: Reset
TRUE: Detected
FALSE: Reset
Recommended
range
-999999 to 999999
-999999 to 999999
0 to 999999
0 to 999999
Type
Data type
Input variable
REAL
Output variable
REAL
Output variable
BOOL
Output variable
BOOL
Initial value
Set by
100.0
User
0.0
User
0.0
User
0.0
User
Data type
REAL
REAL
REAL
REAL

Advertisement