Mitsubishi Electric MELSEC iQ-R Series Programming Manual page 258

Process control function blocks
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

■Variation rate & high/low limiter
This function block checks the variation rate and high/low limits of the input value.
• Variation rate limiter
Variation rate limiter processing result
DML
Execution cycle (ΔT)
Control cycle (CT)
Condition
|T - MV|  DML
T - MV > DML
T - MV < -DML
T: Tentative manipulated value, MV: Manipulated value, DML: Output variation rate high limit value
• High/low limiter
High/low limiter processing result
Execution cycle (ΔT)
Control cycle (CT)
Condition
Variation rate limiter processing result
> MH
Variation rate limiter processing result
< ML
ML  Variation rate limiter processing
result  MH
MH: Output high limit value, ML: Output low limit value
10 LOOP CONTROL OPERATION
256
10.12 Position Type PID Control (Disable Tracking for primary loop/Enable Tracking from secondary loop) (M+P_PIDP_EX_)
Tentative MV value (T)
DML
DML
Control cycle (CT)
Variation rate limiter processing result
T
MV + DML
MV - DML
Variation rate limiter processing value
Control cycle (CT)
High/low limiter processing
result
MH
ML
Variation rate limiter processing value
DML
DML
Control cycle (CT)
Control cycle (CT)
Alarm (ALM)
Output Low Limit Alarm (MLA)
FALSE (Reset)
TRUE (Detected)
FALSE (Reset)
Variation rate limiter
processing value
DML
DML
t
Alarm (ALM)
Output variation rate limit (DMLA)
FALSE (Reset)
TRUE (Detected)
TRUE (Detected)
High/low limiter
processing value
Output high limit
(MH)
Output low limit
(ML)
t
Output High Limit Alarm
(MHA)
TRUE (Detected)
FALSE (Reset)
FALSE (Reset)