Mitsubishi Electric MELSEC iQ-R Series Programming Manual page 437

Process control function blocks
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Setting data
■Input/output variable
Variable name
Description
PVN
Valve opening feedback input
CASIN_T
Primary loop SV input (Unit: %) (With tracking)
(Indirect address)
OPEN_SET
External input of OPEN operation
CLOSE_SET
External input of CLOSE operation
STOP_SET
External input of STOP operation
TO_RST
Time-out error external reset input
OPEN_ST
Open status answer input
CLOSE_ST
Close status answer input
TRIP
External failure (TRIP) input
LOCAL
Local operation selection signal
REMOTE
Remote operation selection signal
OPEN
Open command signal (OPEN) ON output
CLOSE
Close command signal (CLOSE) ON output
■Public variable (operation constant)
Variable name
Description
IN_NMAX
Input High Limit
IN_NMIN
Input Low Limit
IN_HH
High Limit Range Error
IN_H
High Limit Range Error Reset
IN_L
Low Limit Range Error Reset
IN_LL
Low Limit Range Error
DVLS
Large Deviation Alarm Hysteresis
PVTRK_EN
PV Tracking Execution condition
LMTOUT_EN
Output at High or Low Limit of Valve Opening
Execution condition
TRK
Tracking Flag
SVPTN_B0
Setting Value (SV) Used
SVPTN_B1
Setting Value (SV) Pattern
SVLMT_EN
SV High/Low Limiter
*1 When 1 (tracking is executed) is set to the tracking flag, connect CASOUT_T of the primary loop with the input variable CASIN_T.
*1
Recommended range
-999999 to 999999
0 to 100[%]
TRUE, FALSE
FALSE  TRUE: OPEN
TRUE, FALSE
FALSE  TRUE: CLOSE
TRUE, FALSE
(FALSE  TRUE: Sets OPEN and
CLOSE to FALSE)
TRUE, FALSE
FALSE  TRUE: Time-out reset
TRUE: During OPEN output
FALSE: 
TRUE: During CLOSE output
FALSE: 
TRUE: Detected
FALSE: Reset
TRUE: Valid
FALSE: Invalid
TRUE: Valid
FALSE: Invalid
TRUE: Run
FALSE: 
TRUE: Run
FALSE: 
Recommended range
-999999 to 999999
-999999 to 999999
-999999 to 999999
-999999 to 999999
-999999 to 999999
-999999 to 999999
0 to 100
TRUE: Execute
FALSE: Stop
TRUE: Output when PV is 0% or 100%
FALSE: Not output when PV is 0% or
100%
0: Not executed
1: Executed
TRUE: Not used
FALSE: Used
TRUE: Not primary MV
FALSE: Primary MV
TRUE: Execute
FALSE: Not execute
12.39 Position Proportional Output (M+M_PVAL_T_)
Type
Data type
Input variable
REAL
Input variable
DWORD
Input variable
BOOL
Input variable
BOOL
Input variable
BOOL
Input variable
BOOL
Input variable
BOOL
Input variable
BOOL
Input variable
BOOL
Input variable
BOOL
Input variable
BOOL
Output variable
BOOL
Output variable
BOOL
Initial
Set by
Data type
value
100.0
User
REAL
0.0
User
REAL
102.0
User
REAL
100.0
User
REAL
0.0
User
REAL
-2.0
User
REAL
2.0
User
REAL
FALSE
User
BOOL
FALSE
User
BOOL
0
User
INT
TRUE
User
BOOL
TRUE
User
BOOL
FALSE
User
BOOL
12 LOOP TAG
12
435