12.34
Loop Selector (Enable Tracking from secondary
loop to primary loop) (M+M_SEL_T3_)
M+M_SEL_T3_
This FB performs loop selector combining the functions of M+P_SEL_T3_ into a single FB. The primary loop of the input 1
and 2 can be tracked from the secondary loop.
FBD/LD
M+M_SEL_T3_
CASIN_T1
MVN
CASIN_T2
CASOUT_T
SELECT
Applicable tag type
SEL
Control mode
MAN
■Block diagram
MCHG function
(M+P_MCHG)*
CASIN_T1
(%)
(Tracking)
CASIN_T2
(%)
(Tracking)
SELECT
* (M+P_ ) indicates the main structure member tag access FB which is the main component of each function.
Setting data
■Input/output variable
Variable name
Description
CASIN_T1
PV input (Unit: %) (With tracking) (Indirect address)
CASIN_T2
PV input (Unit: %) (With tracking) (Indirect address)
SELECT
Selection signal
MVN
Output to a module
CASOUT_T
Cascade output (Unit: %) (With tracking) (Indirect
address)
12 LOOP TAG
422

12.34 Loop Selector (Enable Tracking from secondary loop to primary loop) (M+M_SEL_T3_)

AUT
CAS
CMV
M+M_SEL_T3_
SEL function
(M+P_SEL_T3_)
Recommended range
0 to 100[%]
0 to 100[%]
TRUE: CASIN_T2
FALSE: CASIN_T1
SEL_NMIN to SEL_NMAX
0 to 100[%]
CSV
(%)
Type
Data type
Input variable
DWORD
Input variable
DWORD
Input variable
BOOL
Output variable
REAL
Output variable
DWORD
MVN
(MV output)
CASOUT_T
(Tracking)

Advertisement