Mitsubishi Electric MELSEC iQ-R Series Programming Manual page 359

Process control function blocks
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

■Public variable (operation constant)
Variable name
Description
IN_NMAX
Input High Limit
IN_NMIN
Input Low Limit
IN_HH
High Limit Range Error
IN_H
High Limit Range Error Reset
IN_L
Low Limit Range Error Reset
IN_LL
Low Limit Range Error
PID2_MTD
Derivative Gain
PID2_DVLS
Large Deviation Alarm Hysteresis
PID2_PN
Reverse Action/Direct Action
*1
PID2_TRK
Tracking Flag
PID2_SVPTN_BO
Setting Value (SV) Used
PID2_SVPTN_B1
Setting Value (SV) Pattern
*1 When 1 (tracking is executed) is set to the tracking flag, connect CASOUT_T of the primary loop with the input variable CASIN_T.
■Public variable (others)
• Simulation processing
Variable name
Description
SIMIN
Simulation Input
• Control mode change processing (MCHG function)
Variable name
Description
MODEIN
Mode Change Signal
E_
Enable Mode Change
*1 Read or write the variables using a program. They are not displayed on "FB Property" of the engineering tool.
■Tag data
For details on tag data that is read or written with this tag FB, refer to the following.
Page 496 2PID
Processing details
This tag FB consists of the following function blocks.
Item
IN function
PHPL function
2PID function
DUTY function
MCHG function
Operation error
An error may occur in a function block that is used in a tag FB. For details on the error, refer to corresponding function blocks.
12.7 2-degree-of-freedom PID Control and DUTY O/P (Enable Tracking for primary loop) (M+M_2PID_DUTY_T)
*1
Function block
M+P_IN
M+P_PHPL
M+P_2PID_T
M+P_DUTY
M+P_MCHG
Recommended
Initial value
range
-999999 to 999999
100.0
-999999 to 999999
0.0
-999999 to 999999
102.0
-999999 to 999999
100.0
-999999 to 999999
0.0
-999999 to 999999
-2.0
0 to 9999
8.0
0 to 100
2.0
0: Reverse action
0
1: Direct action
0: Not executed
0
1: Executed
TRUE: Not used
TRUE
FALSE: Used
TRUE: Not primary MV
TRUE
FALSE: Primary MV
Recommended
Initial value
range
NMIN to NMAX
0.0
Recommended
Initial value
range
1 to 5
0
1: MAN
2: AUT
3: CAS
4: CMV
5: CSV
TRUE: Execute
FALSE
FALSE: Stop
Reference
Page 144 M+P_IN
Page 291 M+P_PHPL
Page 202 M+P_2PID_T
Page 168 M+P_DUTY
Page 338 M+P_MCHG
Set by
Data type
User
REAL
User
REAL
User
REAL
User
REAL
User
REAL
User
REAL
User
REAL
User
REAL
User
INT
User
INT
User
BOOL
User
BOOL
Set by
Data type
User
REAL
Set by
Data type
User
INT
User
BOOL
12 LOOP TAG
357
12