Position Proportional Output (M+M_Pval_T_) - Mitsubishi Electric MELSEC iQ-R Series Programming Manual

Process control function blocks
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

12.39

Position Proportional Output (M+M_PVAL_T_)

M+M_PVAL_T_
This FB outputs open/close command bits to operate the motor valve opening according to the deviation of opening between
the feedback input and setting value. The primary loop can be tracked.
FBD/LD
M+M_PVAL_T_
PVN
OPEN
CASIN_T
CLOSE
OPEN_SET
CLOSE_SET
STOP_SET
TO_RST
OPEN_ST
CLOSE_ST
TRIP
LOCAL
REMOTE
Applicable tag type
PVAL
Control mode
MAN
■Block diagram
MCHG function
(M+P_MCHG)*1
PVN
IN function
(M+P_IN)*1
CASIN_T
(Tracking)
Faceplate
OPEN_SET
OPEN
CLOSE_SET
CLOSE
STOP_SET
STOP
TO_RST
Time-out reset
OPEN_ST
CLOSE_ST
TRIP
LOCAL
REMOTE
Tag data
*1 (M+P_ ) indicates the main structure member tag access FB which is the main component of each function.
*2 For displaying the faceplate status.
*3 Indicates bit item.
12 LOOP TAG
434
12.39 Position Proportional Output (M+M_PVAL_T_)
AUT
PHPL function
PV
(M+P_PHPL)*1
tracking
MAN
MAN
MAN
1)
2)
Tracking
CAS,
(primary loop)
(*2)
CSV
(*2)
SV variation rate
MAN,
high/low limiter
AUT
SV value (target)
SV value (current)
CAS
M+M_PVAL_T_
AUT, CAS
Position
MAN
proportional
output
AUT, CAS
MAN
One-shot output for
command pulse period
One-shot output for
command pulse period
Time-out reset
processing
NOR
SIM, OVR
NOR
SIM, OVR
TRUE
TRK = 1
Disable alarm detection
CMV
OVR
NOR
SIM
OVR
NOR
SIM
SIM/OVER answer back
time delay signal
Time-out
detection
to 1)
to 2)
FALSE
TRUE
Disable alarm detection
(*2)
(*2)
(*2)
(*3)
TRIPA
TOA
ALM
CSV
OPEN
Output exclusion
processing
CLOSE
SIMOUT_OPEN
SIMOUT_CLOSE