Points Time Proportional Output (M+P_Duty_8Pt_) - Mitsubishi Electric MELSEC iQ-R Series Programming Manual

Process control function blocks
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

8.11
8 Points Time Proportional Output
(M+P_DUTY_8PT_)
M+P_DUTY_8PT_
This FB performs output ON time conversion for input values and outputs the result in bits. This FB also adjusts the phase of
output cycles automatically to suppress overlapping of output (for example, peak current).
FBD/LD
M+P_DUTY_8PT_
LINKIN
MVB0
MV0
MVB1
MV1
MVB2
MV2
MVB3
MV3
MVB4
MV4
MVB5
MV5
MVB6
MV6
MVB7
MV7
LINKOUT
■Block diagram
LINKIN
MV0
MV1
MV2
Output 'ON'
conversion
MV3
time
MV4
MV5
MV6
MV7
Setting data
■Input/output variable
Variable
Description
name
LINKIN
Link input (Indirect address)
MV0 to MV7
MV input
MVB0 to MVB7
Bit ON/OFF duty output
LINKOUT
Link output (Indirect address)
■Public variable (operation constant)
Variable
Description
name
PRIMARY
Lead FB specified
CTDUTY
Control Output Cycle
DELAY
Output ON Delay Time
M+P_DUTY_8PT_
Output phase
processing
MVB0
MVB1
MVB2
MVB3
MVB4
MVB5
MVB6
MVB7
LINKOUT
Recommended
Type
range
Input variable
-10 to 110[%]
Input variable
TRUE, FALSE
Output variable
Output variable
Recommended
Initial value
range
TRUE, FALSE
TRUE
0 to 9999[s]
1.0
0 to 9999[s]
0.0

8.11 8 Points Time Proportional Output (M+P_DUTY_8PT_)

Data type
DWORD
REAL
BOOL
DWORD
Set by
Data type
User
BOOL
User
REAL
User
REAL