Mitsubishi Electric MELSEC iQ-R Series Programming Manual page 467

Process control function blocks
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Setting data
■Input/output variable
Variable
Description
name
OPEN_SET
External input for OPEN operation
STOP_SET
External input for STOP operation
CLOSE_SET
External input for CLOSE operation
TO_RST
Time-out error external reset input
OPEN_ST
Status answer input
CLOSE_ST
Status answer input
TRIP
External failure (TRIP) input
LOCAL
Local operation selection signal
REMOTE
Remote operation selection signal
OPEN
ON output for command pulse period
STOP_
ON output for command pulse period
CLOSE
ON output for command pulse period
*1 The default value is FALSE.
■Public variable (others)
• Control mode change processing (MCHG function)
Variable
Description
name
MODEIN
Mode Change Signal
E_
Enable Mode Change
*1 Read or write the variables using a program. They are not displayed on "FB Property" of the engineering tool.
■Tag data
For details on tag data that is read or written with this tag FB, refer to the following.
Page 563 MVAL2
Recommended range
TRUE, FALSE
FALSE  TRUE: OPEN
TRUE, FALSE
FALSE  TRUE: STOP
TRUE, FALSE
FALSE  TRUE: CLOSE
TRUE, FALSE
FALSE  TRUE: Time-out reset
TRUE: OPEN
FALSE: SEMI_CLOSE
TRUE: CLOSE
FALSE: SEMI_CLOSE
TRUE: Detected
FALSE: Reset
TRUE: Valid
FALSE: Invalid
TRUE: Valid
FALSE: Invalid
TRUE: Run
FALSE: 
TRUE: Run
FALSE: 
TRUE: Run
FALSE: 
*1
Recommended range
1, 2
1: MAN
2: AUT
TRUE: Execute
FALSE: Stop
Type
*1
Input variable
*1
Input variable
*1
Input variable
*1
Input variable
Input variable
*1
Input variable
*1
Input variable
*1
Input variable
*1
Input variable
*1
Output variable
*1
Output variable
*1
Output variable
*1
Initial value
0
FALSE
13.4 ON/OFF Operation (2 Input/3 Output) (M+M_MVAL2)
Data type
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
Set by
Data type
User
INT
User
BOOL
13 STATUS TAG
465
13

Advertisement

Table of Contents
loading