M+M_Pidp_Ex - Mitsubishi Electric MELSEC iQ-R Series Programming Manual

Process control function blocks
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

12.14
Position Type PID Control (Disable Tracking for
primary loop/Enable Tracking from secondary
loop) (M+M_PIDP_EX_)

M+M_PIDP_EX_

This FB performs position type PID control combining the functions of M+P_IN, M+P_PHPL, and M+P_PIDP_EX_ into a
single FB.
It also allows manipulated value bumpless switching and tracking from the secondary loop at a change of control mode.
FBD/LD
M+M_PIDP_EX_
PVN
MVN
CASIN
CASOUT
CASOUT_T
Applicable tag type
PIDP
Control mode
MAN
■Block diagram
MCHG function
(M+P_MCHG)*
PVN
IN function
(M+P_IN)*
CASIN
* (M+P_ ) indicates the main structure member tag access FB which is the main component of each function.
Setting data
■Input/output variable
Variable name
Description
PVN
Input from a module
CASIN
Primary loop SV input (Unit: %)
MVN
Output to a module
CASOUT
Cascade MV output (Unit: %)
CASOUT_T
Cascade MV output (Unit: %) (With tracking) (Indirect
address)
12 LOOP TAG
378
12.14 Position Type PID Control (Disable Tracking for primary loop/Enable Tracking from secondary loop) (M+M_PIDP_EX_)
AUT
CAS
M+M_PIDP_EX_
PHPL function
(M+P_PHPL)*
CMV
PIDP function
(M+P_PIDP_EX_)*
Recommended range
Type
-999999 to 999999
Input variable
0 to 100[%]
Input variable
PIDP_NMIN to PIDP_NMAX
Output variable
0 to 100[%]
Output variable
0 to 100[%]
Output variable
CSV
MVN
MV(%)
CASOUT
MV(%)
CASOUT_T
Tracking
Data type
REAL
REAL
REAL
REAL
DWORD