Mitsubishi Electric MELSEC iQ-R Series Programming Manual page 287

Process control function blocks
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

■Disable alarm detection
This function block sets whether to detect alarms (ALM) or not in the deviation check.
Item
Disable alarm detection by setting tag data
Disable alarm detection by loop stop processing
■Loop stop processing
When the stop alarm (SPA) of the alarm (ALM) is TRUE, this function block performs the following processing.
• MV is cleared to 0.
• The control mode is automatically switched to MANUAL.
• When DVLA of the alarm (ALM) has occurred, the DVLA is reset.
• No alarm is detected in the deviation check.
■Processing operation
: Performed, : Not performed
Control mode
Processing operation
Deviation check
MAN, CMV, AUT
CAS, CSV
*1 Tracking is performed when the tracking flag (TRK) is 1.
*2 An alarm whose corresponding bit is TRUE (Valid) in the disable alarm detection (INH) is not detected.
Operation error
Error code
Description
(SD0)
3400H
An invalid operation (such as division by zero) is performed.
3402H
Input data (PVP), operation constant (MTD, DVLS, PN, TRK, SVPTN_B0, SVPTN_B1), or tag data is a subnormal number or NaN (not a
number).
3403H
An overflow has occurred.
3405H
The control cycle (CT) setting is less than 0.
The execution cycle (T) setting is less than 0.
The value divided the control cycle (CT) by the execution cycle (T) exceeds 32767.
Disable alarm detection processing
If the following bits in the disable alarm detection (INH) are TRUE, no DVLA of
the alarm (ALM) will be detected.
• ERRI
• DVLI
Page 285 Loop stop processing
BPI operation
Engineering
value
conversion
10.17 Blend PI Control (Enable Tracking for primary loop) (M+P_BPI_T)
Inverse
Tracking
engineering
value
conversion
*1
10 LOOP CONTROL OPERATION
10
Alarm
*2
*2
285