Mitsubishi Electric MELSEC iQ-R Series Programming Manual page 321

Process control function blocks
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

■Advance function
In the AUT mode, this function block proceeds to the next step by forcibly ending the step in execution.
This function is executed on the rising edge of the input variable ADVANCE command and proceeds the processing by one
step. To proceed the processing by one step next time, turn off the command and then turn it on again.
Setting value (SV)
Skips the remaining time.
SV2
SV1
SV0C
T1_
T2_
T_: In execution
ON
Advance command
OFF
When the advance command is executed in the waiting status, the status is cleared and the processing shifts to the one of the
next step.
When the advance command is executed at the last step, the control will be immediately completed and the setting value
before the execution of the advance command will be held.
■Wait function
In the AUT mode, this function block checks if the process variable (PV) has followed the setting value (SV), and controls the
progress of steps every time each step is completed.
The wait width setting is common to all steps.
Condition
Control mode
Wait Width
MAN
WAIT  0
AUT
WAIT > 0
*1 When the time in the step was changed and the step was completed (T = Tn), the setting value (SVPGS) immediately before the change
of the time in the step is held instead of the last value of the step. To hold the last value of the step (SVn), change the time in the step to
the time immediately before the end of the step (T = Tn - 1).
Setting value (SV)
SV1
Waits until PV value reaches
within wait band when
the step ends.
PV input value
Setting value (SV)
SV1
PV input value
Time (T_)
Process Variable
|PV - SV| > WAIT
|PV - SV|  WAIT
Wait band (WAIT)
T1
T2
Starts the next step
when PV value reaches within wait band.
T1
Waiting
T2
Processing result
The wait function is not executed.
Transition to the next step stops.
The last value of the step is held as the setting value
*1
(SV).
Transition to the next step is performed.
Time (T)
Tn(n=1 to 32)
Time (T)
10 LOOP CONTROL OPERATION
10.25 Multi-Point Program Setter (M+P_PGS2_)