Mitsubishi Electric MELSEC iQ-R Series Programming Manual page 457

Process control function blocks
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Operation error
There is no operation error.
If the STOP command (or RUN command) is issued while a command pulse signal (TRUE) is output from the
output variable RUN (or output variable STOP_), the command pulse signals (TRUE) are output
simultaneously from the output variable RUN and output variable STOP_.
<When command pulse signals (TRUE) are output simultaneously from output variable RUN and
output variable STOP>
RUN command input signal from faceplate or
input RUN_SET (Detected at rising edge)
Command pulse signal from output pin RUN
(output variable RUN)
STOP command input signal from faceplate or
input STOP_SET (Detected at rising edge)
Command pulse signal from output pin STOP_
(output variable STOP_)
When the output variable RUN and output variable STOP_ are output directly to the external device, multiple
commands (RUN command and STOP command) may be output simultaneously to the external device.
Not to output multiple commands to the external device simultaneously, create a program to output only either
one of the command pulse signals to the external device.
Command pulse period (DOT)
Command pulse period (DOT)
: Time when command pulse signals are output
simultaneously (TRUE)
13.1 Motor Irreversible (2 Input/2 Output) (M+M_NREV)
t
t
t
t
13 STATUS TAG
455
13