Technical manual
Binary input and output modules
Binary input
Binary input debounce filter
The debounce filter eliminates bounces and short disturbances on a binary input.
A time counter is used for filtering. The time counter is increased once in a millisecond
when a binary input is high, or decreased when a binary input is low. A new debounced
binary input signal is forwarded when the time counter reaches the set DebounceTime
value and the debounced input value is high or when the time counter reaches 0 and
the debounced input value is low. The default setting of DebounceTime is 1 ms.
The binary input ON-event gets the time stamp of the first rising edge, after which the
counter does not reach 0 again. The same happens when the signal goes down to 0
again.
Oscillation filter
Binary input wiring can be very long in substations and there are electromagnetic
fields from for example nearby breakers. An oscillation filter is used to reduce the
disturbance from the system when a binary input starts oscillating.
An oscillation counter counts the debounced signal state changes during 1 s. If the
counter value is greater than the set value OscBlock, the input signal is blocked. The
input signal is ignored until the oscillation counter value during 1 s is below the set
value OscRelease.
Settings
Setting parameters for binary input modules
Unit
Off
-
On
0.001 - 0.020
s
1 - 40
Hz
1 - 30
Hz
Binary input and output modules
Step
Default
-
On
0.001
0.001
1
40
1
30
Section 4
Description
Operation Off/On
Debounce time for binary inputs
Oscillation block limit
Oscillation release limit
75